VX-3008F.Voice Evacuation Frame 8SS

     PA/Sound System ---    TOA    ---

Previous ‹‹ » Next

VX-3008F.Voice Evacuation Frame 8SS


The VX-3008F is a device designed to control the Voice evacuation announcements of TOA's VX-3000 Series rack-mount type voice evacuation system which is compliant with the European Standard EN54 for fire alarm systems. It has audio input terminals and can output the amplified audio signals to the speaker lines when the optional power amplifier modules are mounted.It is possible to make an Emergency Warning Broadcast assigned a higher priority than the Emergency broadcast. Two patterns of the Emergency broadcast can be activated simultaneously.Compatible with network, the system can be configured in distributed arrangement.Features include the following functions: Digital signal processing function that enables appropriate acoustic adjustment for individual input sound sources and output amplifiers, Feedback suppressor function that automatically suppresses acoustic feedback when it occurs, VOX function that allows start/stop control of broadcast by way of an audio trigger, and ANC function that enables an ambient noise control. (The ANC function distinguishes between the unit's output sound and the ambient noise. The unit's output sound is not detected as noise.) Indicators that show such statuses as fault status and power amplifier signal status are provided. It has 8 speaker output channels. A total of 3 power amplifier modules (2 for zone amplifier use and 1 for standby amplifier use) can be mounted. Equipped with a matrix output, the VX-3008F can be used as 2-bus speaker selector using 2 power amplifiers. Setting the matrix output destination makes 1-bus and 2-bus zones coexist. Zones can be expanded by connecting the unit having amplifier module(s) and the one having no amplifier module. As the VX-3008F is equipped with Standby amplifier input/output terminal, the standby amplifier, when mounted, can be shared among VX-3000F units.

Specifications:



Power Source 20 - 33 V DC, removable terminal block (4 pins)
Power Consumption 24 W (frame only) at 33 V DC input, 90 W (RS Link: 2 A output) at 33 V DC input
Indicators POWER (green) …1, RUN (green) …1, EMERGENCY (red) …1, CPU OFF (red) …1, LAN A (green) …1, LAN B (green) …1, RS LINK A (green) …1, RS LINK B (green) …1
FAULT STATUS (yellow)
GENERAL …1, UNIT …1, NETWORK …1, EMG MIC …1, FUSE …1, POWER …1, CPU …1, ZONE …8
AMPLIFIER
PEAK (red) …3, SIGNAL (green) …3, OPERATE (green) …3, POWER (green) …3
Operation Fault Control Switch …2 (ACK/RESET)
Test Switch …1 (LAMP TEST)
Setting Switch: ID NUMBER, RESET, IMPEDANCE, Setting (internal front panel)
LAN A, B Number of Connectors: 2 (LAN A, LAN B)
Network I/F: 100BASE-TX
Network Protocol: TCP, UDP, ARP, ICMP, RTP, IGMP, FTP, HTTP
Spanning tree Protocol: RSTP
Audio Transmission System: TOA Packet Audio
Audio Encoding Method: PCM
Audio Sampling Frequency: 48 kHz
Audio Quantifying Bit Number: 16 bits
Connection Device: VX-3004F, Other VX-3008F, VX-3016F, NX-300, Switching HUB
Connector: RJ45 connector
Connection Cable: Category 5 twisted pair cable (CAT5)
Number of Stages of Cascade connection: UP to 7
Maximum Cable Distance: 100 m (328.08 ft)
RS Link A, B Number of Connectors: 2 (RS LINK A, RS LINK B)
Audio input level: 0 dB (*2)
Power feed: Max. 1 A per connector
Connector: RJ45 connector
Connection Cable: Shielded Category 5 twisted pair cable (CAT5-STP)
Maximum Cable Distance: 1200 m (3937.01 ft)
DS Link Connection Device: DS LINK of Power supply units
Connector: RJ45 connector
Connection Cable: Shielded Category 5 twisted pair cable (CAT5-STP)
Maximum Cable Distance: 5 m (16.4 ft)
Analog Link Number of Connectors: 1 input, 1 output
Connection Device: VX-3004F, Other VX-3008F, VX-3016F
Connector: RJ45 connector
Connection Cable: Shielded Category 5 twisted pair cable (CAT5-STP)
Maximum Cable Distance: 800 m (2624.67 ft)
Control Input 1, 2 16 inputs, no-voltage make contact input, open voltage: 24 V DC, short-circuit current: 2 mA
Fault Detection System: Short circuit, Open circuit, Method: Voltage detect
Connector: RJ45 connector
Connection Cable: Shielded Category 5 twisted pair cable (CAT5-STP)
Emergency Control IN Input 2: Isolated voltage input, -24 to +24 V
Connector: RJ45 connector
Connection Cable: Category 5 twisted pair cable (CAT5)
VOX Function Threshold: -60 to 0 dB (1 dB steps)
Hysteresis: 0 to +10 dB, Hold time: 10 ms - 10 s
Settable for each audio input
Control Output 1, 2 General outputs : 8 with CONTROL OUTPUT 1
Exclusive outputs : 3 with CONTROL OUTPUT 2 GENERAL FAULT, CPU FAULT, CPU OFF
No-voltage make contact, electrical contact output, control current: 10 mA, withstand voltage: 28 V DC
Connector: RJ45 connector
Connection Cable: Shielded Category 5 twisted pair cable (CAT5-STP)
ATT/Control Output 8 outputs, no-voltage make contact, relay contact (NC, NO, C), control current: 2 mA to 5 A, withstand voltage: 125 V AC, 40 V DC
Connector: Removable terminal block (12 pins) …2
Audio Input 1, 2, 3, 4 4 inputs
Sensitivity:
LINE: -20 dB (*2), MIC: -60 dB (*2)
LINE/MIC/ANC Sensor (changeable with setting software)
Gain Control: volume adjustable with volume control (internal front panel)
- ∞ to 0 dB
Input Impedance: 47 kΩ, electronically-balanced
Frequency Response: 40 Hz - 20 kHz -/+1 dB (at DA CONTROL LINK, 0 dB output)
Distortion: 1% or less (at DA CONTROL LINK, 0 dB output, 1 kHz)
Signal to Noise Ratio: 60 dB or more (at DA CONTROL LINK, A-weighted)
Phantom Power Supply: 24 V DC, can be set with setting software
Connector: Removable terminal block (6 pins) …2

Digital Signal Processing
Feedback Suppression Function 7 filters (auto), Settable for each audio input and RS LINK (A/B)
Equalizer/Filter 3 bands for each audio input and RS LINK (A/B), 6 bands for each amplifier output
Parametric equalizer: 20 Hz - 20 kHz, ±15 dB, Q: 0.267 - 69.249
Filtering: High-pass filter 20 Hz - 20 kHz, 6 dB/oct, 12 dB/oct
              Low-pass filter 20 Hz - 20 kHz, 6 dB/oct, 12 dB/oct
              High shelving filter 6 - 20 kHz, ±15 dB
              Low shelving filter 20 - 500 Hz, ±15 dB
              Notch filter (amplifier output only) 20 Hz - 20 kHz, Q: 8.651 - 69.249
              All-pass filter (amplifier output only) 20 Hz - 20 kHz, Q: 0.267 - 69.249
              Horn equalizer (amplifier output only) 20 kHz, 0 to +18 dB (0.5 dB steps)
Compressor Threshold: -20 to 0 dB (1 dB steps)
Ratio: 1:1, 1.1:1, 1.2:1, 1.3:1, 1.5:1, 1.7:1, 2:1, 2.3:1, 2.6:1, 3:1, 4:1, 5:1, 7:1, 8:1, 10:1, 12:1, 20:1, ∞:1
Attack time: 0.2 ms - 5 s, Release time: 10 ms - 5 s
Gain: - ∞ to +10 dB, Knee type: hard knee, middle knee, soft knee
Delay For each amplifier output, 0 - 2730 ms (0.021 ms steps)
ANC(Ambient Noise Control) Amplifier output level control, Automatic sensor input reference level measuring, Sensor input reference level fine adjustment
Maximum output signal level control: -15 to 0 dB
Minimum output signal level control: -18 to -3 dB
Sample time setting: 10 s, 20 s, 30 s, 1 min, 5 min
Gain ratio setting: (Ambient noise: Output signal level) 6:3, 5:3, 4:3, 3:3, 3:4, 3:5, 3:6
Ambient noise measuring frequency setting: 20 Hz - 20 kHz, 3 points
 
Speaker Line 8 channels, 1 Earth terminal
Maximum Voltage/Current: 100 Vrms, 5 Arms
Connector: Removable terminal block (17 pins) …1
Fault Detection System: Short circuit, Open circuit, Ground fault, Method: Impedance or End of line
Standby Amplifier Input/Output Input: 1, Output: 1
Maximum Voltage/Current: 100 Vrms, 5 Arms
Connector: Removable terminal block (2 pins) …2
Extension Amplifier Input/Output Input: 2, Output: 2
Maximum Voltage/Current: 100 Vrms, 5 Arms
Connector: Removable terminal block (2 pins) …4
Power Amplifier Number of Amplifiers: 3
Connector: DA CONTROL LINK …3, DA OUTPUT LINK …3
Operating Temperature -5 to +45 (23 bF to 113 bF)
Operating Humidity 90 %RH or less (no condensation)
Finish Panel: Surface-treated steel plate, black, 30 % gloss, paint
Dimensions 483 (W) × 132.6 (H) × 345 (D) mm (19.02 × 5.22' × 13.58')'
Weight 7.9 kg (17.42 lb)
Accessory Rack mounting bracket (preinstalled on the unit) …2, Rack mounting screw ...4, CD (PC setting software) …1, Removable terminal plug (2 pins) …6, Removable terminal plug (4 pins) …1, Removable terminal plug (6 pins) …2, Removable terminal plug (12 pins) …2, Removable terminal plug (17 pins) …1, Ferrite clamp …2
 



Brochure : https://cdn1.npcdn.net/attachments/1548639748504e5b3e37a2d6bc037b25622e97a6fc.pdf


Ruijie RG-WALL 1600-M5100 Next-Generation Firewall WG-D100T. TOA Digital Wireless Guide Receiver. #ASIP Connect XP-SR200K Cynics 4ch AHD/TVI Stand-Alone Hybrid DVR + IP.XD3104LS XP-SR40 NVR5216-8P-I. Dahua 16Channel 1U 8PoE AI Network Video Recorder DS-2CE76H0T-ITMFS. Hikvision 5MP Audio Fixed Turret Camera AR881EF_OS.SOYAL MINI FINGERPRINT READER DS-7204HGHI-F1.4CH Tribrid 720P Turbo Digital Video Recoder WD MY CLOUD HOME 2TB - WDBVXC0030HWT MB-TS900.TOA Rack Mount Bracket SR-H3L.TOA Line Array Speaker YP-M5310.Omnidirectional Lavalier Microphone TS-782.TOA Delegate Unit HX-7B-WP.Speaker System TPC-SD8420-TB. Dahua Thermal Network Hybrid Speed Dome Camera EM-800.Gooseneck Microphone uFace 800. ZkTeco Multi-Biometric Time Attendance and Access Control Terminal DP-L2. TOA Digital Ambient Noise Controller. #ASIP Connect KX-NT543.STANDARD IP PHONEt,3 LINES DISPLAY CR-273.Rack E3200. Aluminium Housing Arm